Lumastream Trinity 6 DMX User Manual Page 2

  • Download
  • Add to my manuals
  • Print
  • Page
    / 3
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 1
Trinity 6 DMX Specifications
Input
Output
System Protection
Safety and EMI/EMC
Environmental
Control Interface
Rated Input Voltage 115 to 277 Vac hard wired
Rated Input Frequency 50 - 60 Hz
Power Factor EN61000-3-2 @ 115 or 277 Vac, 100% load, 0.97 W/VA min
Input Current Total Harmonic Distortion @ 115 or 277 Vac, 100% load, 13% max
Rated Output Power @ 40°C / 104°F ambient, 243 W max
Output Voltage 6 to 27 Vdc
Efciency 87% with 100% load @ 277 Vac input
System Power Cycle Delay 2 second typical time required for stabilization of all outputs
Output Current Tolerance +/-5 % of nominal
Output Over voltage, over current, short circuit protection
Over Temperature Power supply will shut down when external ambient temperature
exceeds 43°C/ 109.4°F or case temperature reaches 85°C/ 185°F
nominal.
Output Interconnection Hiccup mode with automatic recovery upon removal of short.
Agency Approvals UL 60950-1, IEC60950-1, SELV, Class 2 outputs, LPS standard UL8750
Conducted and Radiated Emissions EN55022; ICES-003; FCC Title 47, Part 15, Class A (for commercial use
only); EN55015 Conducted (external lter required)
EMC EN61547- general lighting
Location Rating Dry
Operating Ambient Temperature -20°C to 40°C / -4°F to 104°F
Cold Start Temperature -20°C / -4°F
Storage Ambient Temperature -40°C to 80°C / -40°F to 176°F
Relative Humidity 5% to 95% noncondensing
Mean Time Between Failure
(MIL HDBK-217F); (12 channel)
>60,000 hours @ 40°C / 104°F; >97,000 hours @ 25°C / 77°F
Control Method DMX512-A
DMX Receiver Isolation Isolated from earth ground
Start Codes Will only respond to NULL START code
Loss of DMX Input Signal Outputs will go to 100% light intensity in less than 1 second.
LSPS02 / Trinity 6 DMX
© 2014 LumaStream www.lumastream.com +1 (727) 827-2805